نوع محصول یا مولفه تجهیزات
product or component type
Fan, pump, compressor, conveyor
product specific application
Integrated conforming to EN/IEC 61800-3 category C3 with 50 m
[Us] rated supply voltage
45 kW for normal duty37 kW for heavy duty
60 hp for normal duty50 hp for heavy duty
92.9 A at 380 V (normal duty)88.3 A at 415 V (normal duty)80.5 A at 380 V (heavy duty)75.8 A at 415 V (heavy duty)
63.5 kVA at 415 V (normal duty)54.5 kVA at 415 V (heavy duty)
88 A at 4 kHz for normal duty75 A at 4 kHz for heavy duty
continuous output current
97 A during 60 s (normal duty)112 A during 60 s (heavy duty)
maximum transient current
مشخصات کنترل موتور ناهمزمان
Optimized torque modeConstant torque standardVariable torque standard
asynchronous motor control profile
nominal switching frequency
تعداد سرعت از پیش تعیین شده
communication port protocol
Slot A: communication card, Profibus DP V1Slot A: digital or analog I/O extension cardSlot A: relay output card
Automatic whatever the loadAdjustableNot available in permanent magnet motor lawCan be suppressed
Linear adjustable separately from 0.01 to 9000 sS, U or customized
acceleration and deceleration ramps
Thermal protection: motorMotor phase break: motorThermal protection: driveOverheating: driveOvercurrent between output phases and earth: driveOverload of output voltage: driveShort-circuit protection: driveMotor phase break: driveOvervoltages on the DC bus: driveLine supply overvoltage: driveLine supply undervoltage: driveLine supply phase loss: driveOverspeed: driveBreak on the control circuit: drive
Display unit: 0.1 HzAnalog input: 0.012/50 Hz
Control, screw terminal: 0.5...1.5 mm²Line side, screw terminal: 35...50 mm²Motor, screw terminal: 50 mm²
1 RJ45 (on the remote graphic terminal) for Modbus serial
2-wire RS 485 for Modbus serial
4.8, 9.6, 19.2, 38.4 kbit/s for Modbus serial
No impedance for Modbus serial
External supply for digital inputs: 24 V DC (19…30 V), <1.25 mA, protection type: overload and short-circuit protectionInternal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC +/- 5 %, <10 mA, protection type: overload and short-circuit protection
2 LEDs for local diagnostic1 LED (yellow) for embedded communication status2 LEDs (dual colour) for communication module status1 LED (red) for presence of voltage
613 mm706 mm with EMC plate
AI1, AI2, AI3 software-configurable voltage: 0...10 V DC, impedance: 30 kOhm, resolution 12 bitsAI1, AI2, AI3 software-configurable current: 0...20 mA, impedance: 250 Ohm, resolution 12 bitsAI2, AI3 software-configurable temperature probe or water level sensor
DI1...DI6 programmable as logic input, 24 V DC (<= 30 V), impedance: 3.5 kOhmDI5, DI6 programmable as pulse input: 0…30 kHz, 24 V DC (<= 30 V)
DI1...DI6: logic input level 1 PLC conforming to EN/IEC 61131-2DI5, DI6: pulse input level 1 PLC conforming to IEC 65A-68
Positive logic (source): DI1...DI6 configurable logic input, < 5 V (state 0), > 11 V (state 1)Negative logic (sink): DI1...DI6 configurable logic input, > 16 V (state 0), < 10 V (state 1)Positive logic (source): DI5, DI6 configurable pulse input, < 0.6 V (state 0), > 2.5 V (state 1)
Software-configurable current AQ1, AQ2: 0...20 mA, resolution 10 bitsSoftware-configurable voltage AQ1, AQ2: 0...10 V DC impedance 470 Ohm, resolution 10 bits
5 ms +/- 0.1 ms (AI1, AI2, AI3) - analog input2 ms +/- 0.5 ms (DI1...DI6)configurable - discrete input5 ms +/- 1 ms (DI5, DI6)configurable - pulse input10 ms +/- 1 ms (AQ1, AQ2) - analog output
+/- 0.6 % AI1, AI2, AI3 for a temperature variation 60 °C analog input+/- 1 % AQ1, AQ2 for a temperature variation 60 °C analog output
AI1, AI2, AI3: +/- 0.15 % of maximum value for analog inputAQ1, AQ2: +/- 0.2 % for analog output
Configurable relay logic R1: fault relay NO/NC electrical durability 100000 cyclesConfigurable relay logic R2: sequence relay NO electrical durability 100000 cyclesConfigurable relay logic R3: sequence relay NO electrical durability 100000 cycles
Relay output (R1, R2, R3): 5 ms (+/- 0.5 ms)
Relay output R1, R2, R3: 5 mA at 24 V DC
minimum switching current
Relay output R1, R2, R3 on resistive load, cos phi = 1: 3 A at 250 V ACRelay output R1, R2, R3 on resistive load, cos phi = 1: 3 A at 30 V DCRelay output R1, R2, R3 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 250 V ACRelay output R1, R2, R3 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 30 V DC
maximum switching current
Between power and control terminals
> 1 MOhm 500 V DC for 1 minute to earth
75 dB conforming to 86/188/EEC
1000 W(forced convection) at 380 V, switching frequency 4 kHz121 W(natural convection) at 380 V, switching frequency 4 kHz
Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-41.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6
electromagnetic compatibility
2 conforming to EN/IEC 61800-5-1
1.5 mm peak to peak (f= 2…13 Hz) conforming to IEC 60068-2-61 gn (f= 13…200 Hz) conforming to IEC 60068-2-6
15 gn for 11 ms conforming to IEC 60068-2-27
5…95 % without condensation conforming to IEC 60068-2-3
-15…45 °C (without derating)45…60 °C (with derating factor)
ambient air temperature for operation
دمای هوای محیط برای ذخیره سازی
ambient air temperature for storage
<= 1000 m without derating1000...4800 m with current derating 1 % per 100 m
Chemical pollution resistance class 3C3 conforming to EN/IEC 60721-3-3Dust pollution resistance class 3S3 conforming to EN/IEC 60721-3-3
environmental characteristic
EN/IEC 61800-3Environment 2 category C3 EN/IEC 61800-3 EN/IEC 61800-5-1 IEC 60721-3
بخشنامه RoHS اتحادیه اروپا
Pro-active compliance (Product out of EU RoHS legal scope)
EU RoHS Declaration
RoHS exemption information
Product Environmental Profile
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins